Latest News
|NewsletterAlthough much of this discussion can be applied to applications which require battery back-up, such as -48V telecom central-office equipment, AC-DC front ends do not typically include use of battery back-up and therefore do not include battery controllers and associated equipment.
Generally, the requirements for paralleling AC-input front ends also apply to DC-input front ends; the only difference between these units once installed in the end system is the input source. DC-input front ends allow equipment primarily designed to operate from utility-AC inputs to alternatively be operated from the -48V battery-backed supplies commonly found in telecommunications applications.
Paralleling basics
The three primarily reasons for paralleling power supplies are to increase total power, facilitate scalability, and to provide redundancy.
Paralleling for increased power is done when the host-system power requirements cannot be met by a single power supply, or if there are form-factor limitations that preclude the use of one power supply. An example is when two 1U-high power supplies are used instead of a single 2U power supply that would not fit within the height constraint of a 1U-rack.
Although each power supply should equally power its portion of the load, there is always some degree of current-share imbalance. Therefore, supplies must either be designed for paralleling, or the power supplies must use external circuitry to accomplish the task.
Paralleling for scalability is done to provide power supplies which cover both small and large applications. This approach facilitates the addition of incremental power when the needs of an individual site increase, and reduces the number of power-supply model numbers in spares inventory when servicing multiple sites.
Paralleling for redundancy is done because many mission-critical infrastructure systems require very high availability. Applications include medical life support, communications, and air-traffic control. Power systems used in these applications require redundant operation so that in the case of single or multiple power fault conditions, the mission-critical system can operate without interruption.
The circuit diagram shows two power supplies paralleled for redundant operation using OR-ing diodes DO1 and DO2. Although not shown explicitly, this circuit would generally require a current-sharing methodology in order to operate reliably.
Redundancy is generally accomplished by paralleling two or more supplies to ensure that adequate power is available in the event of a power supply failure. Each power supply utilizes OR-ing circuits to isolate the outputs; enabling functioning supplies to work together and effectively disconnecting any defective supply’s output from the paralleled bus. This effectively protects the power bus; increasing the availability of the host system.
Calculating availability in redundant power configurations
Redundant power systems can be implemented in many ways, each having an impact on the availability of the system. Consider the following system designs:
N+M paralleling
The nomenclature used to describe the redundant system in the above examples is called “N+M paralleling”, where for a redundant power system:
If N+M supplies are used to power a system, N are needed to carry the load, and the availability of the power system increases exponentially as M increases.
Typically, N is the number of supplies with output power PSUP, required to power the smallest system, PSYS, or N= (PSYS/PSUP), rounded up to the next higher integer number.
M is the number of “spare” supplies with output power PSUP, determined by the designer as necessary to provide the requisite level of system availability.
A typical method of determining the output power, PSUP, of each power supply is make PSUP = PSYS-MIN, where PSYS-MIN is the power required to power the smallest host system. Adding another supply to this would create a 1+1 redundant system for this provisioning level.
For larger systems, additional power supplies, or power PSUP, are added (N is increased). For instance, the next level of provisioning may require one additional supply to power the system. In this case, the system would operate from a N+M = 2+1 redundant power system. Systems requiring higher power would increase the N count.
Further improvement in availability may also include increasing the number of spares (M) used in the system. Most large systems require M=1 as a minimum, but very high availability systems may specify M=2. However, not many systems today specify M greater than 2, because power supply MTBF has significantly improved over the last few years, and because of cost.
System availability is very dependent on the Mean Time to Repair (MTTR) value of a system. Power supplies designed for use in high-availability environments have monitoring and signaling capabilities which allow external supervisory systems to monitor the operation of each supply and report failures. Failure reporting via dedicated signal lines or protocols such as I2C, allows technicians to quickly locate and replace a failed unit; this functionality minimises the MTTR, and increases system availability and MTBF.
Roy Allen is application engineering manager at Power-One